The new Fluke 705 Loop Calibrator is a cost-effective, integrated solution for calibration, repair and maintenance of current loops. It features:
Specifications |
|
Current Measurement: |
Range: 0 to 24 mA
Resolution: 0.001 mA
Accuracy: 0.02% Rdg + 2 LSD
|
Current Sourcing: |
Range: 0 to 20 mA or 4 to 20 mA
Accuracy: 0.025% Rdg + 2 LSD
Drive Capability: 1000 ¥Ø @ 24 mA |
Current Simulation: |
Range: 0 to 20 mA or 4 to 20 mA
Accuracy: 0.025% Rdg + 2 LSD
Ext. loop voltage requirement: 12-30 V |
Loop Power: |
While measuring mA, 24 V |
Voltage measurement: |
Range: 0 to 28 V DC
Resolution: 1 mV
Accuracy: 0.025% Rdg + 2 LSD |
Environmental Specifications |
|
Operating Temperature: |
14 to 131¡ÆF (-10 to 55 ¨¬C) |
Storage Temperature: |
-40 to 140¡ÆF (-40 to 60 ¨¬C) |
Humidity (Without Condensation): |
0 to 90% 32 to 95¡ÆF (0 to 35 ¨¬C)
0 to 70% 95 to 131¡ÆF (35 to 55 ¨¬C) |
Temperature Coefficient: |
14 to 64.4¡ÆF (-10 to 18 ¨¬C)
82.4 to 131¡ÆF (28 to 55 ¨¬C)
¡¾.005% of range per ¨¬C |
Safety Specifications |
|
Safety: |
CSA C22.2 No. 1010.1:1992 |
EMC: |
EN50082-1:1992 and EN55022:1994 Class B |
Maximum Voltage: |
30 V |
Mechanical & General Specifications |
|
Size: |
5.98" x 2.75" x 1.61" (152 x 70 x 41 mm) |
Weight: |
11.9 oz (340g) |
Batteries: |
One 9V battery |
Warranty: |
Three years |
Shock & Vibration: |
Per MIL-T-28800 for a Class 2 Instrument |