Fluke 975 AirMeter with Velocity

Fluke 975 AirMeter with Velocity
Item #: K610-9751
Manufacturer: Fluke Corporation
Manufacturer Item #: 2666111
Product Type: IAQ Meter
Your Price: $2,495.00
Features & Applications:

The Fluke 975 AirMeter test tool raises indoor air monitoring to the next level by combining five powerful tools in one, rugged and easy-to-use handheld device. Use the Fluke 975 to optimize HVAC ventilation settings for ASHRAE 62 recommendations, actively monitor conditions that promote a productive environment, and quickly and accurately address occupant comfort complaints the first time. The Fluke 975 measures:

  • Temperature
  • Velocity
  • Humidity
  • CO2
  • CO

Features:

The Fluke 975 offers an unparalleled featureset for HVAC and facilities technicians, helping them work more quickly and accurately, with the ease of use and durability customers expect from a Fluke meter.

  • Simultaneously measures, logs, and displays temperature, humidity, CO2, and CO on a bright, backlit LCD display
  • One-touch air flow and velocity with available probe
  • Wet bulb and dew point temperature
  • % of outside air calculation
  • CO2 and CO field calibration feature
  • Monitor needs to be calibrated monthly for CO sensor;
    see Fluke 975 AirMeter Calibration Kit (#K610-9752)
  • Self-test function at startup
  • Auto-backlight
  • Automatically compensates for barometric pressure changes
  • Min/Max/Average on all measured and calculated readings
  • Multi-language user interface
  • Metric or standard units
  • Audible and visual threshold alarms
  • Extensive discrete or continuous data logging capacity, downloadable to PC via USB interface
  • Keypad lock for security
  • Included FlukeView Forms® software
  • Air velocity probe

Spec Summary:

Measured Specicications
Temperature:
Range: -5 to 122°F (-20 to 50°C)
Display resolution: 0.1°F (0.1°C)
Accuracy: ± 0.9°C/± 1.62°F from 40 to 60°C
± 0.5 °C/± 1.00°F from 5 to 40°C
± 1.1 °C/± 1.98°F from -20 to 5°C
Relative humidity:
Range: 10 to 90 % RH, non-condensing
Display Resolution: 1%
Accuracy: ± 2 % RH (10 to 90 % RH)
Air velocity:
Range: 50.0 to 3000 fpm
0.25 to 15 m/sec
1 fpm (0.005m/sec)
Display Resolution:
Accuracy: ±4 % or 4 fpm*
±4 % or 0.02 m/sec* whichever is greater
*Accuracy specification only valid for
velocity readings above 50 fpm.
C0:
Range: 0 to 500 ppm
Display Resolution: 1 ppm
Accuracy: ± 5 % or ± 3 ppm, whichever
is greater, @ 20°C and 50 % RH
C02:
Range: 0 to 5000 ppm
Display Resolution: 1 ppm
Accuracy: Warm up time 1 min (5 minutes
for full specification) 2.75% + 75 ppm
Calculated specifications
Dew point temperature:
Range: -47 to 122°F (-44 to 50°C)
Display resolution: 0.1°F (0.1°C)
Accuracy: ± 1 °C when temp: -20 to 50 °C RH: 40 to 90 %
± 2°C when temp: -20 to 50°C RH: 20 to 40 %
± 4°C when RH: 10 to 20 %
Wet bulb temperature:
Range: 3 to 122°F (-16 to 50°C)
Display Resolution: 0.1 °C, (0.1 °F)
Accuracy: ± 1.2 °C when RH: 20 to 90 % temp: -20 to 60°C
± 2.1 °C when RH: 10 to 20 %
Volume flow rate (in a duct):
Range: 0 to 3,965 M3/m, (0 to 140,000 cfm)
0.001 M3/min, (1 cfm)
Display Resolution:
Accuracy: N/A: The volume flow calculation will be a simple
average of the data points times the duct area
% outside air (based on temperature):
Range: 0 to 100%
Display Resolution: 0.1
% outside air (based on CO2):
Range: 0 to 100 %
Display Resolution: 0.1 % N/A
General specifications
Operating and storage temperature:
4 to 122°F (-20 to 50°C)
Humidity:
10 % to 90 % (non-condensing)
Altitude:
Up to 6562 ft (2000 m)
Shock and vibration:
MIL-PRF-28800F: Class 2
Multi-language interface:
English, French, Spanish, Portuguese and German
Battery:
Three-AA alkaline
Data logging:
25,000 records (continuous), 99 records (discrete)
Warranty:
Two-years