Professional Equipment and our suppliers are dedicated to providing quality products to our customers. We stand behind our commitment to quality with a satisfaction guarantee on every purchase*. If, for any reason, a customer is not satisfied with a product, they may return it within 30 days of the date purchased for a refund of the purchase price of the product(s). Returned merchandise must be in its original box, in new condition and include all instructions, and the invoice or packing slip.
*Exceptions: Videotapes, DVDs, audiotapes, computer software (once opened), animal traps (once opened), forms, reports, custom orders and leased items are not returnable. Books are returnable within 7 days of receipt. Test chemicals, once opened are not returnable. Downloads are non-refundable.
You can download a credit application by clicking here. Please submit your completed credit application via fax or mail. Feel free to contact us at 1-800-334-9291 with any questions.
Features & Applications:
Large backlit LCD displays up to 35 parameters in one screen.
Features:
True RMS power measurements with harmonics display (1-99th order)
Capture 28 Transient events (including Dip, Swell and Outage) with programmable threshold
Simultaneous Harmonics and Waveform display
Display of Waveform with Peak Values
Analysis of Total Harmonic Distortion
Displays Active Power (kW), Apparent Power (kVA), Reactive Power (kVAR) and Power Factor
kWH and kVARh energy measurements
Maximum Demand with programmable period
Current measurements to 1000A with adjustable CT ratio
Voltage measurements to 600V with adjustable VT ratio
Graphical Phase diagram with system parameters
3-phase Voltage or Current Unbalanced Ratio
3-phase Voltage or Current Unbalanced Factor
Calculated Unbalanced Current through Neutral Line
Datalogger records up to 52428 records in single phase, (17476 records in 3-phase)
Optically isolated RS-232 interface with software to
download Waveforms, Power Parameters and Harmonics
Complete with (3) 1000A current clamps, 4 voltage leads with
alligator clips, 8 AA batteries, AC adaptor, software, PC interface
cable, and carrying case
Spec Summary:
Specifications
Range
Basic Accuracy
ACV (True rms):
600V
±(0.5%rdg+5d)
ACA:
1000A
±(0.5%rdg+5d)
Active Power (kW):
9.999MW
±(1%rdg+8d)
Apparent Power (kVA):
9999kVA
VA=Vrms x Arms
Power Factor:
0.0 to +1.00
±(1.5%°rdg±8d)
Frequency:
45-65Hz
0.1Hz
Phase:
-180.0°~ 0°~ +180.0°
±1°
Harmonics:
1 to 99
±2%
Crest Factor:
1.00 to 99.99
±(5%+30d)
Peak AC Voltage accuracy:
±(5%rdg+30d)
Peak AC Current accuracy:
±(5%rdg+30d)
Active Power Energy (kWh)
0mWh to 999,999kWh
Reactive Power Energy (kVARh):
0.0kVARh to 1000MWh
Datalogging:
52428 records (single phase)/17476
records (3 phase)