Get quick & easy interpretation of readings with the Fluke-707Ex Intrinsically Safe Loop Calibrator

Item #: P609-7071
Manufacturer: Fluke Electronics
Manufacturer Item #: Fluke-707Ex
Product Type: Electrical Calibrators

Your Price $1,047.95

 Write a Review

Purchase this product with Fluke Premium Tool Bag for only $81.95 more!

Features & Applications:

The Fluke-707Ex Intrinsically Safe Loop Calibrator is an intrinsically safe loop calibrator that is made for use in explosion endangered areas. The Fluke 707Ex is certified in accordance with the ATEX directive (Ex II 2 G Eex ia IIC T4) in Zones 1 and 2. This calibrator has a number of useful features and a large display. It is also easy to use with one hand.

Features:

  • Large display and simple, quick-click push rotary button for easy one-handed operation
  • Simultaneous mA and % readout for quick, easy, interpretation of readings
  • mA accuracy of 0.015%, superior to other loop calibrators
  • 1 µA resolution for mA source, simulate and measure
  • Push button with 25% steps for fast, easy linearity checks
  • 0-100% "span check" for fast confirmation of zero and span
  • Selectable slow ramp, fast ramp, and step ramp to provide smooth outputs for valve slewing and loop functional tests
  • Internal loop supply, so you can power and read a transmitter at the same time without carrying a DMM
  • Measures Vdc to 28 V
  • Single 9 V battery that is easily changed
  • 0-20 mA or 4-20 mA default start up modes
  • Innovative output adjustment dial with 1 µA and 100 µA resolution
  • HART® compatible resistance is connected in series with the loop supply for compatibility with HART communicators

Spec Summary:

Specifications
Current Measurement:
Range: 0 to 24 mA
Resolution: 0.001 mA
Accuracy: 0.015% Rdg + 2 LSD
Current Sourcing:
Range: 0 to 20 mA or 4 to 20 mA
Accuracy: 0.015% Rdg + 2 LSD
Drive Capability: 700 Ù at 20 mA
Current Simulation:
Range: 0 to 20 mA or 4 to 20 mA
Accuracy: 0.015% Rdg + 2 LSD
Loop Power:
While measuring mA, 24 V
Voltage measurement:
Range: 0 to 28 V DC
Resolution: 1 mV
Accuracy: 0.015% Rdg + 2 LSD
Environmental Specifications
Operating Temperature:
14 to 131°F (-10 to 55°C)
Storage Temperature:
-40 to 140°F (-40 to 60°C)
Humidity (Without Condensation):
0 to 95% 32 to 86°F (0 to 30°C)
0 to 75% 86 to 104°F (30 to 40°C)
0 to 45% 104 to 122°F (40 to 50°C)
Temperature Coefficient:
-10 to 18°C, 28 to 55°C, ±.005% of range per °C
Safety Specifications
Safety:
CSA C22.2 No. 1010.1:1992
EMC:
EN50082-1:1992 and EN55022:1994 Class B
Maximum voltage:
30 V (protection circuit for 230 V)
ATEX certification:
Ex II G Eex ia IIC T4 Zones 1 and 2, ZELM 02 ATEX 0120 X
CE certification:
EN61010-1 and EN61326
Mechanical & General Specifications
Size:
5.98" x 2.75" x 1.61" (152 x 70 x 41 mm)
Weight:
7.9 oz (12.3 oz including holster)
[224 g (350 g including holster)]
Batteries:
One 9V battery Alkaline
Warranty:
One year
Shock & Vibration:
Per MIL-T-28800 for a Class 2 Instrument
Fluke-707Ex Intrinsically Safe Loop Calibrator Manual

Click the link(s) above to open the document(s) for this item. Should you wish to download it, right click on the link and select "Save Target As..." or "Save Link As...".

If you do not have Acrobat Reader, click here to download the latest version.
Fluke-707Ex Intrinsically Safe Loop Calibrator

Fluke-707Ex Intrinsically Safe Loop Calibrator

Buy Now

Purchase this product with Fluke Premium Tool Bag for only $81.95 more!