Professional Equipment and our suppliers are dedicated to providing quality products to our customers. We stand behind our commitment to quality with a satisfaction guarantee on every purchase*. If, for any reason, a customer is not satisfied with a product, they may return it within 30 days of the date purchased for a refund of the purchase price of the product(s). Returned merchandise must be in its original box, in new condition and include all instructions, and the invoice or packing slip.
*Exceptions: Videotapes, DVDs, audiotapes, computer software (once opened), animal traps (once opened), forms, reports, custom orders and leased items are not returnable. Books are returnable within 7 days of receipt. Test chemicals, once opened are not returnable. Downloads are non-refundable.
The 707Ex is an intrinsically safe loop calibrator for use in explosion endangered areas. The Fluke 707Ex is certified in accordance with the ATEX directive (Ex II 2 G Eex ia IIC T4) in Zones 1 and 2.
Features:
Large display and simple, quick-click push rotary button for easy one-handed operation
Simultaneous mA and % readout for quick, easy, interpretation of readings
mA accuracy of 0.015%, superior to other loop calibrators
1 µA resolution for mA source, simulate and measure
Push button with 25% steps for fast, easy linearity checks
0-100% "span check" for fast confirmation of zero and span
Selectable slow ramp, fast ramp, and step ramp to provide smooth outputs for valve slewing and loop functional tests
Internal loop supply, so you can power and read a transmitter at the same time without carrying a DMM
Measures Vdc to 28 V
Single 9 V battery that is easily changed
0-20 mA or 4-20 mA default start up modes
Innovative output adjustment dial with 1 µA and 100 µA resolution
HART® compatible resistance is connected in series with the loop supply for compatibility with HART communicators
Spec Summary:
Specifications
Current Measurement:
Range: 0 to 24 mA
Resolution: 0.001 mA
Accuracy: 0.015% Rdg + 2 LSD
Current Sourcing:
Range: 0 to 20 mA or 4 to 20 mA
Accuracy: 0.015% Rdg + 2 LSD
Drive Capability: 700 Ù at 20 mA
Current Simulation:
Range: 0 to 20 mA or 4 to 20 mA
Accuracy: 0.015% Rdg + 2 LSD
Loop Power:
While measuring mA, 24 V
Voltage measurement:
Range: 0 to 28 V DC
Resolution: 1 mV
Accuracy: 0.015% Rdg + 2 LSD
Environmental Specifications
Operating Temperature:
14 to 131°F (-10 to 55°C)
Storage Temperature:
-40 to 140°F (-40 to 60°C)
Humidity (Without Condensation):
0 to 95% 32 to 86°F (0 to 30°C)
0 to 75% 86 to 104°F (30 to 40°C)
0 to 45% 104 to 122°F (40 to 50°C)
Temperature Coefficient:
-10 to 18°C, 28 to 55°C, ±.005% of range per °C
Safety Specifications
Safety:
CSA C22.2 No. 1010.1:1992
EMC:
EN50082-1:1992 and EN55022:1994 Class B
Maximum voltage:
30 V (protection circuit for 230 V)
ATEX certification:
Ex II G Eex ia IIC T4 Zones 1 and 2, ZELM 02 ATEX 0120 X
CE certification:
EN61010-1 and EN61326
Mechanical & General Specifications
Size:
5.98" x 2.75" x 1.61" (152 x 70 x 41 mm)
Weight:
7.9 oz (12.3 oz including holster)
[224 g (350 g including holster)]