Features & Applications:
The Amprobe Anemometer Thermometer is ideal for HVAC/R technicians measuring heat, ventilation, air conditioning, refrigeration, wind flow, or temperature in residential, commercial and industrial air conditioning systems.
Use this multi-functional tool to check air velocity FPM (Feet per minute), air volume (flow), and CFM (Cubic feet per minute). The remote vane allows for greater measurement location flexibility. Switch between °C and °F, and input the area of airflow measurement to gain accurate air velocity results. Measure an air flow source for a continuous moving average for up to two hours. Determine minimum, maximum and average readings from a single point air source.
Features a large dual display to view both air flow or velocity measurement plus temperature. Has a long extended flexible cord for remote vane access capabilities.
Shipped in a deluxe hard carrying case to protect and transport your Anemometer.
Features:
- Anemometer with flexible precision vane
- Input surface area for airflow measurements
- Flexible vane sensor
- Accurate Thermistor for temperature measurements
- Continuous moving average results for up to 2 hours
- MIN/MAX/AVG readings
- Air velocity average for multiple points
- Temperature in °C or °F
- Data hold to freeze measurement display of both readings
- Auto power off function
- Deluxe hard carrying case
Spec Summary:
| Specifications |
Display: |
| Dual 4-digit (9999 count) LCD |
|
|
Measurement units: |
| Air velocity: |
ft/min (feet per minute); m/s (meters per second) |
| Air flow: |
CMS (m 3/sec) and CFM (ft 3/min) |
| Temperature: |
°C and °F |
|
Data hold: |
| Freezes displayed reading |
|
|
Sensors: |
| Air velocity/flow sensor: |
Conventional angled vane arms with low friction ball bearing |
| Temperature sensor: |
Precision thermistor |
|
MIN/MAX memory: |
| Record and view minimum and maximum readings |
|
|
Average reading memory: |
| Single Point (up to 2 hours) or Multi-Point (up to 8 readings) |
|
|
Automatic power off: |
| Sleep mode (with bypass) after 20 mins. conserves energy |
|
|
Operating temperature: |
|
Operating humidity: |
|
Power supply: |
| 9 V battery (Heavy duty alkaline) |
|
|
Battery life: |
|
Weight: |
| 0.8 lb (363 g) including battery and sensor |
|
|
Dimensions: |
| Main instrument: |
7.1" x 2.8" x 1.4" (181 x 71 x 38 mm) |
| Sensor head diameter |
70 mm |
|
Air Velocity: |
| Measurements |
m/s (meters per sec) |
|
ft/min (feet per minute) |
| Range |
0.40 to 25.00 m/s |
|
125 to 4900 ft/min |
| Resolution |
0.01m/s |
|
1 ft/min |
| Accuracy |
± 2 % of full scale |
|
± 2 % of full scale |
|
Air Flow: |
| Measurements |
CMS (cubic meters per sec.) |
|
CFM (cubic feet per minute) |
| Range |
0.01 0.01 to 99.99 m3 /sec |
|
1 to 9999 ft3 /min |
| Resolution |
0.01 |
|
1.0 |
| Area |
0 to 9.999 m |
|
0 to 9.999 ft |
|
Air Temperature: |
| Measurements |
°C (°F) |
| Range |
0 to 50°C (32 to 122°F) |
| Resolution |
0.1°C/(°F) |
| Accuracy |
± 0.8°C (1.5°F) |
|