Fluke 983 Particle Counter is the preferred choice for HVAC and IAQ professionals!
Click here to view Particle Counter Shop and Compare chart
Features & Applications:
This environmental testing equipment is the portable solution for determining airborne particle concentrations. From filter testing to IAQ investigations, the Fluke 983 can be utilized for immediate response to occupant complaints, or as part of a comprehensive preventive maintenance program. The Fluke 983 Particle Counter simultaneously measures and displays six channels of particle size distribution, temperature and humidity. The air testing unit features expanded data logging and a six-channel particle size display.
Run more tests quickly and efficiently, and spend less time spent cycling through screens to obtain the data. Lightweight and easy to use in any position, the Fluke 983 features a rugged rubber holster and comfortable hand strap. This environmental testing equipment is compact, lightweight, and allows for one-handed operation. The Fluke 983 can be utilized in any position with complete accuracy, and the 8 hour rechargeable battery allows you to perform air testing surveys uninterrupted. A large, 5000 sample record capacity makes the Fluke 983 the ideal tool for tracking down a particle source or determining size distribution of airborne particles.
Features:
- Simultaneously measure and display 6 channel of particle sizes, temperature and humidity
- Measure particle size down to 0.3 µm
- Selectable sample time, count data, programmable delay
- Store 5000 records of date, time, counts, relative humidity, temperature, sample volumes, alarms and location label
- Upload stored data to a PC with included software
- Compact, self-contained package allows for one-handed operation
- Intuitive, easy to use user interface
- Always ready to run, with no fluids to refill
- Backlit LCD for use in any lighting condition
- 8 hour rechargeable NiMH battery
- Protective holster
Applications:
- Measure filter efficiency
- Monitor industrial cleanrooms
- Pre-screen indoor air quality and confidently work with IAQ specialists
- Locate particle sources for remediation
- Report the effectiveness of repairs to customers
- Drive additional business by demonstrating the need for maintenance and repair
Spec Summary:
| Specifications |
| Channels: |
0.3, 0.5, 1.0, 2.0, 5.0, 10.0 µm |
| Flow Rate: |
0.1 cfm (2.83 L/min) controlled by internal pump |
| Count Modes: |
Concentration, totalize, audio |
| Counting Efficiency: |
50% @0.3 µm; 100% for particles > 0.45 µm
(per JIS B9921:1997) |
| Zero Count: |
1 count/5 minute (JIS B9921:1997) |
| Coincidence Loss: |
5% at 2,000,000 particles per ft3 |
| Relative Humidity: |
± 7%, 20% to 90% non-condensing |
| Temperature: |
50 to 104˚F (± 3˚C, 10 to 40˚C) |
| Data Storage: |
5000 sample records (rotating buffer) of date,
time, counts,
relative humidity,
temperature,
sample volumes, alarms, label |
| Alarms: |
Counts, low battery, sensor fail |
| Delay Time: |
0 to 24 hours |
| Sample Inlet: |
Isokinetic probe |
| Interface: |
RS-232 and RS-485 via RJ-45 |
| Environmental Specifications: |
| Operating: |
50 to 104˚F (10 to 40˚C), 20 to 90% relative humidity,
non-condensing |
| Storage: |
14 to 122˚F (-10 to 50˚C), up to 90% relative humidity,
non-condensing |
| Mechanical & General Specifications: |
| Size: |
4.5 in x 8.25 in x 2.25 in (11.43 x 20.96 x 5.72 cm)
Dimensions (W x L x D) |
| Weight: |
2.2 lbs (1.0 kg) |
| Power: |
AC adapter, 12 V DC at 2.5A, 90 to 250 V AC,
50 to 60 Hz |
| Rechargeable: |
NiMH, 4.8 V at 4.5 Ah; replaceable |
| Battery Life: |
8 hours |
| Recharge Time: |
2 hours |
| Calibration: |
PSL particles in air (NIST traceable) |
|