Fluke 1503 Insulation Resistance Tester (500-1000V)

Fluke 1503 Insulation Resistance Tester (500-1000V)
Item #: E605-1503
Manufacturer: Fluke Electronics
Manufacturer Item #: 2427883
Product Type: Megohmmeters
Your Price: $425.95
In Stock

Fluke's 1503 Insulation Resistance Tester is packed with features to help you save time and money

Features & Applications:

Quickly tackle troubleshooting, commissioning and preventative maintenance tasks with this reliable tool. Live-circuit detection and auto-discharge of apactive voltage keep you safer on the job.

Features:

  • Insulation test range: 0.1 MΩ to 2000 MΩ
  • Insulation test voltages: 500 V, 1000 V
  • Repetitive or hard-to-reach testing is easy with the remote test probe
  • Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
  • Auto-discharge of capacitive voltage for added user protection
  • AC/DC voltage: 0.1 V to 600 V
  • 200 mA Continuity
  • Resistance: 0.01 to 20.00 kohms
  • Save battery power with auto power off
  • Read measurements easily with large, backlit display
  • CAT IV 600 V overvoltage category rating for added user protection
  • Remote probe, test leads, probes and alligator clips included with each tester
  • Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
  • Four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests
  • One year warranty

Spec Summary:

AC/DC Voltage Measurement
Accuracy: Range
Resolution
50Hz to 400Hz ±(%of Rdg+Digits)
600.0V
0.1V
±2%+3
Input impedance: 3 Mohms (nominal), < 100 pF
Common mode rejection
ratio (1 kohms unbalanced):
> 60 dB at dc, 50 or 60 Hz
Overload Protection: 600 V rms or dc
Earth bond resistance measurement
Range/Resolution:

20.00 Ω 0.01Ω 200.0Ω 0.1Ω
2000Ω 1.0Ω
20.00Ω 0.01Ω

Accuracy: ± (1.5 % + 3)
Overload Protection: 2 V rms or dc
Open Circuit Test Voltage: > 4.0 V, < 8 V
Short circuit current: > 200.0 mA
Insulation specifications
Measurement range: 0.01 MΩ to 2000 MΩ
Test voltages: 500V, 1000V
Test Voltage Accuracy: +20%, -0%
Short circuit current: 1 mA nominal
Auto Discharge: Discharge time < 0.5 second for C= 1µF or less
Live circuit indicator: Inhibit test if terminal voltage > 30 V prior to
initialization of test
Maximum Capacitive Load: Operable with up to 1 µF load
Measure Accuracy:

50 V: ±(3 % + 5)
100 V: ±(3 % + 5)
250 V: ±(1.5 % + 5)
500 V: ±(1.5 % + 5)
1000 V: ±(1.5 % + 5) to 2000 MΩ, ±(10 % + 3) above MΩ

General Specifications
Maximum voltage applied
to any terminal:
600 V ac rms or dc
Storage Temperature: -40 to 140°F (-40 to 60°C)
Operating Temperature: -4 to 131°F (-20 to 55°C)
Temperature Coefficient: 0.05 x (specified accuracy) per °F for temperatures
< 64°F or > 82°F (< 18°C or > 28°C)
Relative Humidity: 0 to 95 % @ 50 to 86°F (10 to 30°C)
0 to 75 % @ 86 to 104°F (30 to 40°C)
0 to 40 % @ 104 to 131°F (40 to 55°C)
Vibration: Random, 2 g, 5-500 Hz per MIL-PRF-28800F,
Class 2 instrument
Shock: 1 meter drop per IEC 61010-1 2nd Edition
(1 meter drop test, six sides, oak floor)
Electromagnetic compatability: In an RF field of 3 V/M, accuracy =
specified accuracy (EN 61326-1:1997)
Safety: Complies with ANSI/ISA 82.02.01 (61010-1) 2004,
CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN
61010-1 2nd Edition for measurement category IV
600 V (CAT IV)
Certifications: CSA per standard CSA/CAN C22.2
No. 61010.1-04; TUV per standard
IEC/EN 61010-1 2nd Edition
Batteries: Four AA batteries (NEDA 15A or IEC LR6)
Battery Life: Insulation test use: Tester can perform at least 1000
insulation tests with fresh alkaline batteries at room
temperature. These are standard tests of 1000 V
into 1 MΩ with a duty cycle of 5 seconds on
and 25 seconds off.
Resistance measurements: Tester can perform at
least 2500 earth bond resistance measurements
with fresh alkaline batteries at room temperature.
These are standard tests of 1 Ω with a duty cycle
of 5 seconds on and 25 seconds off.
Size: 1.97 in H x 3.94 in W x 8.00 in L
(5.0 cm H x 10.0 cm W x 20.3 cm L)
Weight: 1.2 lb (550 g)
IP Rating: IP40
Altitude: Operating: 2000 m CAT IV 600 V,
3000 m CAT III 600 V
Non-operating (storage): 12,000 m
Over-range capability: 110 % of range
Included Accessories: TL224 Test Leads, TP74 Test Probes,
clips PN 1958654 (red) and PN 1958646
(black), holster and remote probe
Close Window