Professional Equipment     Print Page
PO Box 5197
Janesville, WI 53547-5197

Phone Number: 608-743-8002
Fax Number: 608-743-8039
Toll Free Number: 1-800-334-9291
Toll Free Fax Number: 1-888-776-3187


Fluke 1507 Insulation Resistance Tester (50 - 1000V)

Fluke 1507 Insulation Resistance Tester (50 - 1000V)
Item #: E605-1507
Manufacturer: Fluke Corporation
Manufacturer Item #: 1507
Product Type: Megohmmeters
Your Price: $406.95
In Stock

Fluke's 1507 Insulation Resistance Tester is packed with features to help you save time and money
Features & Applications:

The Fluke 1507 Insulation Tester is compact, rugged, reliable, and easy to use. With its multiple test voltages, the 1507 is ideal for many troubleshooting, commissioning, and preventative maintenance applications.

Additional features, like the remote probe on these tools save both time and money when performing tests.

Features:

  • Insulation test range: 0.01 MΩ to 10 GΩ
  • Insulation test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V
  • Save both time and money with Automatic calculation of Polarization Index and Dielectric Absorption Ratio
  • Make repetitive tests simple and easy with the 1507's Compare (Pass/Fail) function
  • Repetitive or hard-to-reach testing is easy with the remote test probe
  • Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
  • Auto-discharge of capacitive voltage for added user protection
  • AC/DC voltage: 0.1 V to 600 V
  • 200 mA Continuity
  • Resistance: 0.01 to 20.00 kohms
  • Save battery power with auto power off
  • Read measurements easily with large, backlit display
  • CAT IV 600 V overvoltage category rating for added user protection
  • Remote probe, test leads, probes and alligator clips included with each tester
  • Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
  • Four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests
  • One year warranty

Spec Summary:

AC/DC Voltage Measurement
Accuracy:
Range
Resolution
50Hz to 400Hz±(%of Rdg+Digits)
600.0V
0.1V
±2%+3
Input impedance:
3 Mohms (nominal), < 100 pF
Common mode rejection
ratio (1 kohms unbalanced):
> 60 dB at dc, 50 or 60 Hz
Overload Protection:
600 V rms or dc

Earth bond resistance measurement
Range/Resolution:

20.00 Ω 0.01Ω 200.0Ω 0.1Ω
2000Ω 1.0Ω
20.00Ω 0.01Ω

Accuracy:
± (1.5 % + 3)
Overload Protection:
2 V rms or dc
Open Circuit Test Voltage:
> 4.0 V, < 8 V
Short circuit current:
> 200.0 mA

Insulation specifications
Measurement range:
0.01 MΩ to 10 GΩ
Test voltages:
50 V, 100 V, 250 V, 500 V, 1000 V
Test Voltage Accuracy:
+20%, -0%
Short circuit current:
1 mA nominal
Auto Discharge:
Discharge time < 0.5 second for C= 1µF or less
Live circuit indicator:
Inhibit test if terminal voltage > 30 V prior to
initialization of test
Maximum Capacitive Load:
Operable with up to 1 µF load
Measure Accuracy:

50 V: ±(3 % + 5)
100 V: ±(3 % + 5)
250 V: ±(1.5 % + 5)
500 V: ±(1.5 % + 5)
1000 V: ±(1.5 % + 5) to 2000 MΩ, ±(10 % + 3) above MΩ

General Specifications
Maximum voltage applied
to any terminal:
600 V ac rms or dc
Storage Temperature:
-40 to 140°F (-40 to 60°C)
Operating Temperature:
-4 to 131°F (-20 to 55°C)
Temperature Coefficient:
0.05 x (specified accuracy) per °F for temperatures
< 64°F or > 82°F (< 18°C or > 28°C)
Relative Humidity:
0 to 95 % @ 50 to 86°F (10 to 30°C)
0 to 75 % @ 86 to 104°F (30 to 40°C)
0 to 40 % @ 104 to 131°F (40 to 55°C)
Vibration:
Random, 2 g, 5-500 Hz per MIL-PRF-28800F,
Class 2 instrument
Shock:
1 meter drop per IEC 61010-1 2nd Edition
(1 meter drop test, six sides, oak floor)
Electromagnetic compatability:
In an RF field of 3 V/M, accuracy =
specified accuracy (EN 61326-1:1997)
Safety:
Complies with ANSI/ISA 82.02.01 (61010-1) 2004,
CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN
61010-1 2nd Edition for measurement category IV
600 V (CAT IV)
Certifications:
CSA per standard CSA/CAN C22.2
No. 61010.1-04; TUV per standard
IEC/EN 61010-1 2nd Edition
Batteries:
Four AA batteries (NEDA 15A or IEC LR6)
Battery Life:
Insulation test use: Tester can perform at least 1000
insulation tests with fresh alkaline batteries at room
temperature. These are standard tests of 1000 V
into 1 MΩ with a duty cycle of 5 seconds on
and 25 seconds off.
Resistance measurements: Tester can perform at
least 2500 earth bond resistance measurements
with fresh alkaline batteries at room temperature.
These are standard tests of 1 Ω with a duty cycle
of 5 seconds on and 25 seconds off.
Size:
1.97 in H x 3.94 in W x 8.00 in L
(5.0 cm H x 10.0 cm W x 20.3 cm L)
Weight:
1.2 lb (550 g)
IP Rating:
IP40
Altitude:
Operating: 2000 m CAT IV 600 V,
3000 m CAT III 600 V
Non-operating (storage): 12,000 m
Over-range capability:
110 % of range
Included Accessories:
TL224 Test Leads, TP74 Test Probes,
clips PN 1958654 (red) and PN 1958646
(black), holster and remote probe
Close Window