Features & Applications:
A great deal of information lies hidden behind the vibrating
needle of a typical pressure gauge. Is the TEV valve
modulating properly, or is there liquid flooding back in the
system?
Digi-Cool offers unprecedented diagnostic power with the
Digital Refrigeration System Analyzer (DRSA). The
patented pressure bar graphs allow you to see pressure
dynamics intuitively for quick diagnosis. Automatic
saturation, subcooling and superheat readings mean no
more wallet cards. Conceived by a technician with
modern engineering, the unit will endure years of field use.
The new DRSA-1100 features an integrated temperature
probe to automatically calculate superheat and
subcooling, and pressure extremes monitoring for simple
pressure controls set-up, for even greater convenience
during start-ups.
Features:
- Includes profiles for 23 common refrigerants within:
R-12 R-22 R-134A R-290
R-401A R-401B R-402A R-402B
R-404A R-406A R-407C R-408A
R-409A R-410A R-414B R-416A
R-417A R-420A R-422A R-502
R-507 R-508B R-600A
- "Dynamic Offset" bar graph clearly shows modulation of
control valves, system behavior and faults
- New: Temperature probe for automatic superheat and
subcooling readings
- New: Max and min pressure monitoring for control set-up
- Auto zero key eliminates manual recalibration
- Detects vacuums in Hg
- Easy to read LCD screen with large digits
- Upgradeable for additional refrigerants
- Splash resistant and wide temperature range for indoor &
outdoor use; case resistant to typical oils, acids and sun
exposure
- Advanced, durable tool for the
professional HVAC&R technician
- Service Manifold not included
- New: Sleeker shape
- Protective rubber boot
Spec Summary:
Accuracy: |
0.5% F.S. ± 1 least significant digit, calibration traceable to NIST |
Pressure Ports: |
1/8" NPT supplied with swivel joints and street elbows to fit your manifold |
Working Pressure: |
Low side: 0-200psia (1350 kPa) High side: 0-550psia (3000 kPa) |
Proof Pressure: |
Low side: 600psia (4100 kPa) High side: 1500psia (10300 kPa) |
Burst Pressure: |
Low side: 2000psia (13500 kPa) High side: 5000psia (34500 kPa) |
Temperature Sense: |
-40 to 250°F (-40 to 125°C), ±0.9°F (±0.5°C) between 32 to 158°F (0 to 70°C) |
Usage Environment: |
Indoor/Outdoor AMBIENT TEMPERATURE: -4 to 122°F (-20 to 50°C) |
Moisture Exposure: |
Dew, splash and rain resistant; do not immerse in water |
Power Supply: |
9V battery |
Weight: |
1.6lb (740g) |
Battery Life: |
approx. 6 months under normal use |
Dimensions: |
7.3 x 4.9 x 2.7" (18.5 x 12.5 x 6.8cm) |