The Fluke 561 HVACPro Infrared Thermometer replaces several other test tools!
Features & Applications:
The Fluke 561 HVACPro Infrared Thermometer combines a wide range of temperature measurement functions into one compact tool, saving you ample space in your toolbox and allowing you to work more efficiently. Inspect heating, ventilation, air conditioning and refrigeration systems and get both non-contact and contact temperature measurements easily and efficiently.
Features laser-guided sighting for IR measurements!
The IR mode allows you to take temperatures within two meters of the target and scan ducts from a distance or from below without the use of a ladder. The laser sighting system guides measurements with a single laser dot that indicates the approximate center of the measurement area, which becomes larger with distance.
Features:
- Use the infrared (IR) thermometer to measure hot, moving, electrically energized and hard-to-reach objects instantly
- Check motors, insulation, breakers, radiant heating, pipes, corroded connections and wires plus scan ducts in the ceiling from the floor without a ladder
- Handy Velcro pipe probe included for superheat and sub-cooling contact measurements
- Or plug in your own industry-standard K-type thermocouple probes and get the most out of your tool investments
- IR thermometer for quick measurements up close or at a distance, without a ladder
- Compatible with all standard mini-connector K-type thermocouples
- Velcro pipe probe for superheat, sub-cooling or other contact and ambient measurements
- Single-point laser sighting
- Temperature range optimized for HVAC/R applications
- Easy emissivity adjustment for measuring pipes and ducts more accurately
- Lightweight (only 340 grams (12 ounces)) and portable
- Very easy to use
- Efficient – no need to shut down equipment when making IR measurements
- MIN, MAX and DIF temperature readings help you quickly identify problems
- Scan large areas or small objects quickly and efficiently
- HVAC/R measurement guide included to maximize your productivity
Spec Summary:
| Temperature: |
-40 to 1022°F (-40 to 550°C) |
| Display Resolution: |
0.1°F (0.1°C) of reading |
| D:S (Distance to spot size): |
12:1 |
| Easy Emissivity Selector: |
Adjustable with three settings:
Low (0.3), Medium (0.7). High (0.95) |
Display Accuracy
[Assumes ambient
operating temperature of
73°F (23°C) to 77 °F(25°C)]: |
±1.0 % of reading ±1 % of reading or
±2°F (±1°C), whichever is greater below
32°F/0°C, ±2°F (±1°C) ± 0.1°/1° |
| Response Time: |
500 mSec (95 % of reading) |
| Repeatability: |
±0.5 % of reading or ±2°F (±1°C),
whichever is greater |
| Spectral Response: |
8 µm to 14 µm |
| Laser Sighting: |
Single point laser |
| Laser Shutoff: |
Laser turns off above ambient temperature of 104°F (40°C) |
| Laser Power: |
Class 2(II) operation; Output <1mW, wavelength 630-670 nm |
| Relative Humidity: |
10 to 90 % RH non-condensing, at <86°F (30°C) |
| Power: |
2 AA batteries (alkaline or NiCD) |
| Battery Life: |
12 hours |
| Display Hold: |
7 seconds |
| Backlit Display: |
Yes, LCD with dual temperatures (current and MAX/MIN/DIF/KTC),
low battery, F/C indicator, and Scan/Hold options |
| Warranty: |
2 years |
| Operating Temperature: |
32 to 120 °F (0 to 50 °C) |
| Storage Temperature: |
-25 to 150 °F (-20 to 65 °C) |
| Thermocouple Type K Mini Adapter Input: |
Yes, compatible with industry standard K type probes with
mini-connector. |
| Thermocouple Type K Velcro Pipe Probe: |
Yes, with a temperature range of 32 to 212°F (0 to 100°C)
and accuracy of ±4°F (±2.2°C) |
|