Keep your exits marked even during blackouts with the Lightguard Emergency Exit Light Sign!
Features & Applications:
This easy to install, versatile Lightguard Emergency Exit Light Sign provides a wide range of mounting options and features an appealing housing made from UL 94 V-0 high-impact thermoplastic. The Emergency Exit Sign provides emergency illumination via two high-performance lamp reflectors, each adjustable to 180° vertically and horizontally, both integral to the housing. The exit face is illuminated by high-output LEDs, and the light also comes with maintenance-free, sealed batteries which provide an expected life of up to 10 years for lead calcium with an operating range of 65°F (19°C) to 85°F (30°C). Brownout protection activates light when AC voltage drops 20% below nominal. 120/277V AC dual voltage input and surge protection.
Compliance: UL 924 listed, NFPA 70 and 101. NEC, BOCA and OSHA illumination standard.
Features:
Housing
- Contractor-friendly, snap-together back-plate and housing
- Provisions are available for utility supply via 1/2 surface conduit
- UL 94 V-0, 5 VA high impact thermoplastic
- Available in black or white
- Thermoplastic back-plate includes mounting knockouts for easy
installation to standard junction boxes
- Stencil face is easily removed for maintenance
- Field selectable chevrons can be installed and/or removed from
outside the exit housing
- Canopy furnished with all models
Battery
- Batteries are installed and connected to the charger system at
the factory
- Maintenance free, sealed lead calcium battery has an
expected service life of 5 years with an operating range of
65°F (19°C) to 85°F (30°C)
Illumination
- Emergency illumination is provided by two high performance
lamp reflector systems integral to the product housing
- Each lamp reflector system can be adjusted 180° vertically,
and 180° horizontally
- Standard lamp reflector system uses a high intensity 5.4 watt
T-5 wedge base tungsten lamp (7 and 12 watt halogen lamps available)
- High impact polycarbonate diffuser utilizes linear frosted sections
to control sight-line glare and maximize reflector efficiency
- Illumination of the exit face is accomplished with long
lasting, high output Light Emitting Diodes (LEDs)
- Hot spots and striations are eliminated by the internal light
chamber especially designed around the high performance LED
array
- LED and support electronics have an expected service life of 25 years
Electronics
- 120/277 VAC dual voltage input with surge protection
- Lead calcium units utilize a solid-state, fully automatic,
voltage regulated charger
- Nickel cadmium units utilize a solid-state, constant current
charger
- Brownout protection activates lights when AC voltage drops
20% below nominal
- Labor saving AC lockout feature
- Low voltage disconnect switch (LVD) prevents deep battery
discharge
Applications:
- Ideal for commercial, retail, and office locations where an
attractive, highly reliable and easily installed combination
emergency/exit sign is needed
Spec Summary:
| Electrical Specifications |
|
Input power requirements: |
12 watt unit = 0.114 amps (120 VAC),
0.054 amps (277 VAC)
14 - 25 watt units = 0.118 amps (120 VAC),
0.056 amps (277 VAC) |
Code Compliance: |
UL 924 listed
UL damp location listing optional
NFPA 101
NEC, BOCA and OSHA illumination standard |
Warranty: |
Electronics: 3 years
Batteries: 1 year full, 4 years pro-rata (lead calcium)
5 years full, 5 years pro-rata (nickel cadmium) |