You'll get constant, reliable emergency exit lighting for over a decade with this Emergency Exit Light Sign!
Features & Applications:
This reliable Lightguard Emergency Exit Light Sign features maintenance-free, sealed batteries that deliver an expected life of up to 12 years. An appealing design and low power consumption are just some of the benefits you'll find with this feature-rich exit sign. Along with easy installation, multiple mounting options and two high-performance lamp reflectors, the full features are detailed below.
Compliance: UL 924 listed, NFPA 70 and 101. NEC, BOCA and OSHA illumination standard.
Features:
Housing
- Contractor-friendly, snap-together backplate and housing
- Provisions are available for utility supply via 1/2 surface conduit
- UL 94 V-0, 5 VA high impact thermoplastic
- Available in black or white
- Thermoplastic backplate includes mounting knockouts for easy
installation to standard junction boxes
- Stencil face is easily removed for maintenance
- Field selectable chevrons can be installed and/or removed from
outside the exit housing
- Canopy furnished with all models
Battery
- Batteries are installed and connected to the charger system at
the factory
- Maintenance free, sealed nickel cadmium battery has an
expected service life of 10 years with an operating range of
20°F (-7°C) to 95°F (35°C)
- Nickel cadmium batteries are ideal for high ambient
temperature areas
Illumination
- Emergency illumination is provided by two high performance
lamp reflector systems integral to the product housing
- Each lamp reflector system can be adjusted 180° vertically,
and 180° horizontally
- Standard lamp reflector system uses a high intensity 5.4 watt
T-5 wedge base tungsten lamp (7 and 12 watt halogen lamps available)
- High impact polycarbonate diffuser utilizes linear frosted sections
to control sight-line glare and maximize reflector efficiency
- Illumination of the exit face is accomplished with long
lasting, high output Light Emitting Diodes (LEDs)
- Hot spots and striations are eliminated by the internal light
chamber especially designed around the high performance LED
array
- LED and support electronics have an expected service life of 25 years
Electronics
- 120/277 VAC dual voltage input with surge protection
- Lead calcium units utilize a solid-state, fully automatic,
voltage regulated charger
- Nickel cadmium units utilize a solid-state, constant current
charger
- Brownout protection activates lights when AC voltage drops
20% below nominal
- Labor saving AC lockout feature
- Low voltage disconnect switch (LVD) prevents deep battery
discharge
Applications:
- Ideal for commercial, retail, and office locations where an
attractive, highly reliable and easily installed combination
emergency/exit sign is needed
Spec Summary:
| Electrical Specifications |
|
Input power requirements: |
12 watt unit = 0.114 amps (120 VAC),
0.054 amps (277 VAC)
14 - 25 watt units = 0.118 amps (120 VAC),
0.056 amps (277 VAC) |
Code Compliance: |
UL 924 listed
UL damp location listing optional
NFPA 101
NEC, BOCA and OSHA illumination standard |
Warranty: |
Electronics: 3 years
Batteries: 1 year full, 4 years pro-rata (lead calcium)
5 years full, 5 years pro-rata (nickel cadmium) |
|