Fluke 435 - Power Quality Analyzer 3 Phase - w/o Probe

Fluke 435 - Power Quality Analyzer 3 Phase - w/o Probe
Item #: 148358
Manufacturer: Fluke Electronics
Manufacturer Item #: 2806318 FLUKE 435
Your Price: $7,176.95
This Fluke 435 Power Quality Analyzer will detect and prevent power quality issues before they cause downtime!

Features & Applications:

The Fluke 435 Three-Phase Power Quality Analyzer without Probe helps you locate, predict, prevent and troubleshoot problems in power distribution systems. This easy-to-use power quality tool is a “must have” for any person who maintains or troubleshoots three-phase power. The new IEC Class A standards for flicker and power quality are built right in to take the guess work out of power monitoring.

Features:

  • Troubleshoot real-time: Analyze the trends using the cursors and zoom tools-even while background recording continues
  • Highest safety rating in the industry: 600 V Cat IV/1000 V CAT III rated for use at the service entrance
  • Automatic transient mode: Captures 200 kHz waveform data on all phases simultaneously: Up to 6 kV
  • Fully Class A compliant: Conduct tests according to the stringent international IEC 61000-4-30 Class A standard
  • Measure all three phases and neutral: With included four current probes
  • AutoTrend: Every measurement you see is always automatically recorded, without any setup
  • System-monitor: Up to seven power quality parameters on one screen according to EN50160 power quality standard
  • Inrush mode: For troubleshooting nuisance circuit breaker tripping
  • View graphs and generate reports: With included analysis software
  • Logger function: Configure for any test condition with memory for over 400 parameters at user defined intervals
  • Mains signaling: Measure interference from ripple control signals at specific frequencies
  • Battery Life: Seven hours operating time per charge on NiMH battery pack
  • Warranty: Rugged, handheld troubleshooter with Fluke three-year warranty

Applications:

  • Frontline troubleshooting – quickly diagnose problems on-screen to get your operation back online
  • Predictive maintenance – detect and prevent power quality issues before they cause downtime
  • Quality of service compliance – validate incoming power quality at the service entrance
  • Long-term analysis – uncover hard-to-find or intermittent issues
  • Load studies – verify electrical system capacity before adding loads
  • Energy assessments – quantify energy consumption before and after improvements to justify energy saving devices

Spec Summary:

Technical Data
Inputs
Number: 4 voltage and current (3 phases + neutral)
Maximum voltage: 1000 Vrms (6 kV peak)
Maximum sampling speed: 200 kS/s on each channel simultaneously
Volt/Amps/Hertz
Vrms (AC + DC)
Measurement range: 1 ... 1000 V
Accuracy: 0.1% of Vnom

Vpeak
Measurement range: 1 ... 1400 V
Accuracy: 5% of Vnom

Crest factor, voltage
Measurement range: 1.0 ... > 2.8
Accuracy: ±5%

Arms (AC + DC)
Measurement range: 0 ... 20 kA
Accuracy: ±0.5% ± 5 counts

Apeak
Measurement range: 0 ... 5.5 kA
Accuracy: 5%

Crest factor, A
Measurement range: 1 ... 10
Accuracy: ±5%

Hz 50 Hz nominal
Measurement range: 42.50 ... 57.50 Hz
Accuracy: ±0.01 Hz
Dips and swells
Vrms (AC+DC) ²
Measurement range: 0.0% … 100% of Vnom
Accuracy: ±0.2% of nominal voltage

Arms (AC+DC) ²
Measurement range: 0 ... 20 kA 
Accuracy: ±1% ± 5 counts
Harmonics
Harmonic (interharmonic) (n)
Measurement range: DC, 1..50; (Off, 1..49) measured according to IEC 61000-4-7

Vrms
Measurement range: 0.0 … 1000 V
Accuracy: ±0.05% of nominal voltage

Arms
Measurement range: 0.0 … 4000 mV x clamp scaling
Accuracy: ±5% ± 5 counts

Watts
Measurement range: Depends on clamp scaling and voltage
Accuracy: ±5% ± n x 2% or reading, ± 10 counts

DC voltage
Measurement range: 0.0 … 1000 V
Accuracy: ±0.2% of nominal voltage

THD
Measurement range: 0.0 … 100.0%
Accuracy: ±2.5% V and A (± 5% Watt)

Hz
Measurement range: 0 … 3500 Hz
Accuracy: ± 1 Hz

Phase angle
Measurement range: -360º ... +360º
Accuracy: ± n × 1.5º
Power and energy
Watt, VA, VAR
Measurement range: 1.0 … 20.00 MVA¹
Accuracy: ±1% ± counts

kWh, kVAh, kVARh
Measurement range: 00.00 …200.0 GVAh¹
Accuracy: ± 1.5% ± 10 counts

Power Factor/ Cos Ф / DPF
Measurement range: 0…1
Accuracy: ± 0.03
Flicker
Pst (1 min), Pst, Plt, PF5
Measurement range: 0.00 … 20.00
Accuracy: ±5%
Unbalance
Volts
Measurement range: 0.0 … 5.0%
Accuracy: ±0.5%

Current
Measurement range: 0.0 … 20%
Accuracy: ± 1%
Transient Capture
Volts
Measurement range: ±6000 V
Accuracy: ±2.5% of Vrms
Minimum detect duration 5 µs (200kS/s sampling)
Inrush mode
Arms (AC+DC)
Measurement range: 0.000 … 20.00 kA¹
Accuracy: ±1% of meas ± 5 counts

Inrush duration (selectable)
Measurement range: 7.5 s ... 30 min
Accuracy: ±20 ms (Fnom = 50 Hz)
Autotrend recording
Sampling: 5 readings/sec continuous sampling per channel
Memory: 1800 min, max and avg points for each reading
Recording time: Up to 450 days
Zoom: Up to 12x horizontal zoom
Memory
Screens & data: 50, shared memory divided between logging, screens and data sets
Notes
¹ Depending on clamp scaling
² Value is measured over 1 cycle, commencing at a fundamental zero crossing, and refreshed each half-cycle

The advanced functions Interharmonics, Energy, Transients and Inrush are optional for the Fluke 434 and standard available on the Fluke 435.

Environmental Specifications
Operating Temperature
0 ºC to +50 ºC

Safety Specifications
Safety
EN61010-1 (2nd edition) pollution degree 2; 1000 V CAT III / 600 V CAT IV ANSI/ISA S82.01

Mechanical & General Specifications
Size
256 x 169 x 64 mm
Weight
1.1 kg
Battery Life
Rechargeable NiMH pack (installed): >7 hours
Battery charging time: 4 hours typical
Shock & Vibration
Shock: 30 g
Vibration: 3 g according to MIL-PRF-28800F Class 2
Case
Rugged, shock proof with integrated protective holster, IP51 (drip and dust proof)
Warranty
3 years

Note: Probes not included

Close Window